VLT® HVAC Drive FC 131
Programming Guide
0-11 Programming Set-up
Default value: [9] Active Set-up
Conversion index: -
Select the setup to be edited. It indicates the setup being programmed by LCP when it is accessed by LCP. It indicates the setup
being programmed by RS485 when accessed by RS485, and so on for other channels like fieldbus, USB, and so on.
Table 19: Option:
[1]
Set-up 1
[2]
Set-up 2
[9]
Active Set-up
0-12 Link Setups
Default value: [20] Linked
Conversion index: -
If the setups are not linked, a change between them is not possible while the motor is running.
Table 20: Option:
[0]
Not linked
When selecting a different setup for operation, the setup change does not occur until the motor is coasted.
[20]
Linked
Copy not changeable during operation parameters from 1 setup to the other. It is possible to switch setups
while the motor is running.
4.2.3 0-3* LCP Custom Readout
Parameters for configuring the custom readout value and defining custom display texts. It is possible to customize the display ele-
ments for various purposes.
Custom readout
The calculated value to be shown is based on settings in parameter 0-30 Custom Readout Unit, parameter 0-31 Custom Readout Min
Value (linear only), parameter 0-32 Custom Readout Max Value, parameter 4-14 Motor Speed High Limit [Hz], and actual speed.
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
0
Illustration 6: Custom Readout
The relation depends on the type of unit selected in parameter 0-30 Custom Readout Unit:
Danfoss A/S © 2022.05
Parameter type: Option
Data type: u_int8
Edit setup 1.
Edit setup 2.
Edit parameters in the setup selected via digital I/Os.
Parameter type: Option
Data type: u_int8
Motor Speed
Motor Speed
High limit
P 4-14 (Hz)
2-setup: 1 setup
Change during operation: True
2-setup: All setups
Change during operation: False
AU370727746889en-000101 / 130R0994 | 37
Parameters