Danfoss VLT HVAC Drive FC 131 Programming Manual page 94

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
6-90 Terminal 42 Mode
Default value: [0] 0-20 mA
Conversion index: -
Set terminal 45 to act as analog output or as digital output.
Table 172: Option:
[0]
[1]
[2]
6-91 Terminal 42 Analog Output
Default value: [0] No operation
Conversion index: -
Select the function of terminal 42 as an analog current output. See also parameter 6-90 Terminal 42 Mode.
Table 173: Option:
[0]
[100]
[101]
[102]
[103]
[106]
[139]
[184]
[185]
[254]
6-92 Terminal 42 Digital Output
Default value: [0] No operation
Conversion index: -
Select the function of terminal 42 as a digital current output. See also parameter 6-90 Terminal 42 Mode. See parameter 5-40 Function
Relay for description of the options.
Table 174: Option:
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby/no warning
94 | Danfoss A/S © 2022.05
Parameter type: Option
Data type: u_int8
0-20 mA
4-20 mA
Digital output
Parameter type: Option
Data type: u_int8
No operation
Output frequency
Reference
Feedback
Motor current
Power
Bus control
Mirror AI53 mA
Mirror AI54 mA
DC link voltage
Parameter type: Option
Data type: u_int8
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
AU370727746889en-000101 / 130R0994
Parameters