VLT® HVAC Drive FC 131
Programming Guide
[42]
Auto Reset Trip
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
4.10.5 13-5* States
Parameters for programming the smart logic controller.
13-51 SL Controller Event
Default value: [0] False
Conversion index: -
Select the boolean input (True or False) to define the smart logic controller event. See parameter 13-02 Stop Event for further descrip-
tions of options and their functions.
Table 227: Option:
[0]
[1]
[2]
[3]
[4]
[7]
[8]
[9]
[16]
[17]
[18]
120 | Danfoss A/S © 2022.05
This logic rule is True if the drive is tripped (but not trip-locked) and an automatic reset is issued.
Use the result of comparator 4 in the logic rule.
Use the result of comparator 5 in the logic rule.
Use the result of logic rule 4 in the logic rule.
Use the result of logic rule 5 in the logic rule.
Use the result of timer 3 in the logic rule.
Use the result of timer 4 in the logic rule.
Use the result of timer 5 in the logic rule.
Use the result of timer 6 in the logic rule.
Use the result of timer 7 in the logic rule.
A dry-pump condition has been detected. Enable this function in parameter 22-26 Dry Pump Func-
tion.
An end-of-curve condition has been detected. Enable this function in parameter 22-50 End of Curve
Function.
A broken-belt condition has been detected. Enable this function in parameter 22-60 Broken Belt
Function.
Parameter type: Option
Data type: u_int8
False
True
Running
In range
On reference
Out of current range
Below I low
Above I high
Thermal warning
Mains out of range
Reversing
2-setup: 1 setup
Change during operation: True
AU370727746889en-000101 / 130R0994
Parameters