VLT® HVAC Drive FC 131
Programming Guide
[5]
BACnet
[20]
LEN
[24]
Vertiv MB Con-
verter
8-31 Address
Default value: Configuration dependent
Conversion index: -
Enter the address for the RS485 port. Valid range: 1–126 for FC-bus OR 1– 247 for Modbus.
Table 184: Range:
Min: 0.0
Max: 247
8-32 Baud Rate
Default value: -
Conversion index: -
Select the baud rate for the RS485 port. Default value refers to the FC protocol. Changing the protocol in parameter 8-30 Protocol
may change the baud rate.
Table 185: Option:
[0]
2400 Baud
[1]
4800 Baud
[2]
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
8-33 Parity / Stop Bits
Default value: [0] Even parity, 1 stop bit
Conversion index: -
Parity and stop bits for the protocol using the FC port. For some of the protocols, not all options are available. Default value refers to
the FC protocol. Changing the protocol in parameter 8-30 Protocol may change the baud rate.
Danfoss A/S © 2022.05
Communication according to the BACNet protocol.
Communication according to the LEN protocol.
Communication according to the Vertiv MB Converter protocol.
Parameter type: Range
Data type: u_int8
Default value: Configuration dependent
Parameter type: Option
Data type: u_int8
Default setting for FLN.
Default setting for:
BACnet.
Metasys N2.
Default setting for Modbus RTU.
Parameter type: Option
Data type: u_int8
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
AU370727746889en-000101 / 130R0994 | 99
Parameters