You need to configure a routing table
to specify the path from the left
PLC-5/40C processor to the right
PLC-5/40C processor.
Publication 1756-6.5.13 - September 1999
e. Enter the following configuration:
IP Address
Subnet Mask
Gateway Address
Enable Bootp
f. Click on Apply to download the configuration to the module.
Configure the routing table in the 1756-DHRIO module in the left
chassis:
a. From the File menu in the configuration software, select Browse
Network.
b. Select the AB_KT_1 Data Highway Plus driver and double-click on the
1756-DHRIO module.
c. Select the Routing Table Configuration tab.
If you have previously configured any routing tables, click on Restore
Defaults to remove the configuration and restore the default values.
d. Double-click on the 1756-DHRIO module in the routing table.
130.130.130.1
255.255.0.0
0.0.0.0
Unchecked (disabled)