What You Need To Do
Verify the communication driver
configurations (page 7-1).
Test the KTX driver and system
hardware (page 7-2).
Configure the communication
modules (page 7-3).
Connect to the PLC-5/40C
processor (page 7-6).
Initiate Ethernet to DH+ Communication
In this application, you will establish communication between the PC
workstation and the PLC-5/40C processor bridging across Ethernet and
DH+. Change your existing system to the following configuration.
DH+ Network
(link 100)
1756-DHRIO Module
(in slot 1)
DH+ Network
(link 101)
In this example, you communicate with a PLC-5/40C processor on a DH+
network via an Ethernet gateway.
Important: To establish communication between the PC workstation and
the PLC-5/40C via ethernet, you must first configure the
1756-ENET module. The configuration can be sent to the
1756-ENET module over another network, such as ControlNet.
In this example, you will do the configuration over the DH+
network.

Verify the KTX Driver Configuration

Verify that the KTX driver and ethernet driver are configured as directed on
page 3-2.
PC Workstation
(DH+ node 0
Ethernet IP address 130.130.130.1)
Ethernet Network
node 3
(channel A)
node 4
(channel B)
1756-ENET Module
(in slot 2)
Ethernet IP address 130.130.130.2)
PLC-5/40C Processor
(node 10)
Publication 1756-6.5.13 - September 1999
7
Chapter