Chapter 8 What You Need To Do - Allen-Bradley AB QUALITY ControlLogix 1756 Series User Manual

Table of Contents

Advertisement

What You Need To Do
Verify the communication module
node addresses (page 8-2).
Verify the PLC-5/40C processors'
node addresses (page 8-2).
Verify the KTX driver configuration
(page 8-2).
Test the hardware (page 8-2).
Routing table considerations
(page 8-3).
Edit the message instruction
(page 8-3).
Test the application (page 8-6).
Initiate ControlNet to ControlNet
Communication
In this chapter, you will establish communication between two PLC-5/40C
processors, bridging over two ControlNet networks. Change your existing
system to the following configuration.
1756-DHRIO Module
(in slot 2)
1756-CNB Module
(in slot 0)
ControlNet node 11
ControlNet Network #1
PLC-5/40C Processor
(ControlNet node 1)
In this example, you send a PLC-5 Typed Write message from the
PLC-5/40C processor at ControlNet node 1, network 1, to the PLC-5/40C
processor at ControlNet node 2, network 2.
Note that the multi-hop feature described in this chapter requires series
E/D.1 or F/A.1 processors and RSLogix5 software, version 3.2 or greater.
PC Workstation
(DH+ node 0)
DH+ node 3
(channel A)
1756-CNB Module
(in slot 3)
ControlNet node 12
ControlNet Network #2
MSG
PLC-5/40C Processor
(ControlNet node 2)
Publication 1756-6.5.13 - September 1999