e. When the System Communications tab reappears, click on the Online
button.
f. If no program is loaded in the PLC-5/40C processor, a pop-up window
will appear with the message "You cannot go Online to DEFAULT
program." Enter a new processor name of your choice (e.g., "Receiver")
and click on OK.
• Disregard any warnings about ControlNet devices.
• It is not necessary to save the program.
g. Double-click on N7 in the data file list.
You should see the following screen:
Verify that this value is being updated.
When you see N7:0 being updated at one second intervals the message is
being sent successfully from the PLC-5/40C processor at ControlNet node 1
to the PLC-5/40C processor at ControlNet node 2.
Initiate ControlNet to ControlNet Communication
Publication 1756-6.5.13 - September 1999
8-9