Structure Of Cc-Link Ie Tsn Class B/A Devices Only - Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Structure of CC-Link IE TSN Class B/A devices only

Connection of inverters (Only the master station is CC-Link IE TSN Class B.)
■If a switching hub is used to configure a system (master station: 1 Gbps)
The following figure shows connection of the Motion module (1 Gbps) + inverters. (Only the master station is CC-Link IE TSN
Class B.)
No.0
Class B (1 Gbps)
No.0: Motion module (master station)
No.1, No.2, No.3, No.4, No.5: Inverter (remote station)
• When all the device stations are CC-Link IE TSN Class A, they can be connected up to the maximum
number of connectable stations specified in the CC-Link IE TSN performance specifications.
• If the firmware version is "1.001" or earlier, use a general-purpose switching hub that supports the
communication speed of 1 Gbps/100 Mbps to convert the communication speed.
• If the firmware version is "1.002" or later, use a TSN switching hub or general-purpose switching hub that
supports the communication speed of 1 Gbps/100 Mbps to convert the communication speed to 100 Mbps.
When using a TSN switching hub, set "TSN HUB Setting" to "Use TSN HUB".
• Connection after the TSN switching hub or general-purpose switching hub can be a line topology, star
topology, and coexistence of line and star topologies.
• Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In "Network Configuration Settings" under "Basic Settings", set
"Communication Period Setting" of the inverters to "Low-Speed".
■If a switching hub is not used to configure a system (master station: 100 Mbps)
The following figure shows connection of the Motion module (100 Mbps) + inverters. (Only the master station is CC-Link IE
TSN Class B.)
No.0
No.1
Class B (100 Mbps)
Class A (100 Mbps)
No.0: Motion module (master station)
No.1, No.2, No.3, No.4, No.5: Inverter (remote station)
No.1
Class A (100 Mbps)
General-purpose
switching hub
or
TSN switching hub
No.2
No.3
Class A (100 Mbps)
Class A (100 Mbps)
No.2
Class A (100 Mbps)
No.4
Class A (100 Mbps)
No.4
Class A (100 Mbps)
4 SYSTEM CONFIGURATION
4.5 Connection Examples
No.3
Class A (100 Mbps)
No.5
Class A (100 Mbps)
No.5
Class A (100 Mbps)