Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 149

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
1802H
During data link, overlapping IP addresses
have been detected.
1803H
Over the number of stations that can be
connected.
1804H
During data link, invalid connection
structure has been detected.
• A CC-Link IE TSN Class B station is
connected further on the end side than a
CC-Link IE TSN Class A station.
• With the master station with a
communication speed of 1 Gbps, further
on the end side than a station with a
communication speed of 100 Mbps, a
station with a communication speed of 1
Gbps is connected.
• With the master station with a
communication speed of 1 Gbps, there
is a 100 Mbps station whose
communication cycle setting is set to
Basic Period or Normal-Speed (4 times).
• With the master station with a
communication speed of 1 Gbps, a 1
Gbps station is connected.
• For a master station with a
communication speed of 100 Mbps,
"Communication Period Setting" of the
CC-Link IE TSN Class B station with a
communication speed of 100 Mbps is set
to "Low-Speed".
• The communication speed of the master
station and local station are not
matched.
■Multicast mode
• A CC-Link IE TSN Class A local station
is connected further on the end side than
a CC-Link IE TSN Class A remote
station.
• With the master station with a
communication speed of 1 Gbps,
stations with a communication speed of
1 Gbps and 100 Mbps are connected on
the end side via the switching hub.
Action
Change the IP address of devices with a duplicated IP address.
Reduce the number of CC-Link IE TSN Class B devices and TSN
switching hubs to eight or less in total in the transmission path from
the master station to the CC-Link IE TSN Class B device of the end.
Check the connection and setting on the end side of the station
shown in detailed information 2 and take the following actions.
• Connect the CC-Link IE TSN Class A station further on the end
than the CC-Link IE TSN Class B station.
• If the master station has a communication speed of 1 Gbps,
connect the station with a communication speed of 1 Gbps on
the master station side rather than on the side where a station
with a communication speed of 100 Mbps is connected.
• If the master station has a communication speed of 1 Gbps, set
"Communication Period Setting" to "Low-Speed" for the station
with a communication speed of 100 Mbps.
• If the master station has a communication speed of 1 Gbps, set
the station with a communication speed of 100 Mbps as a
standard station.
• If the master station has a communication speed of 100 Mbps,
set the communication speed of the device station to 100 Mbps.
• If the master station has a communication speed of 100 Mbps,
set "Communication Period Setting" of the CC-Link IE TSN Class
B station with a communication speed of 100 Mbps to "Basic
Period" or "Normal-Speed" (4).
• Set the same communication speed for the master station and
local station.
■Multicast mode
• Connect the CC-Link IE TSN Class A remote station further on
the end than the CC-Link IE TSN Class A local station.
• If the master station has a communication speed of 1 Gbps, do
not connect a station with a communication speed of 1 Gbps and
100 Mbps on the end side via the switching hub.
Detailed information 1
Detailed information 2
■Operation source information
• IP address
■IP address duplication
information
• Duplication station 1 MAC
address (1st octet, 2nd
octet)
• Duplication station 1 MAC
address (3rd octet, 4th
octet)
• Duplication station 1 MAC
address (5th octet, 6th octet)
• Duplication station 2 MAC
address (1st octet, 2nd
octet)
• Duplication station 2 MAC
address (3rd octet, 4th
octet)
• Duplication station 2 MAC
address (5th octet, 6th octet)
■Own station information
• Intelligent module No.
• Network No.
• Station No.
• IP address
■Target station information
• Network No.
• Station No.
• IP address
8 TROUBLESHOOTING
147
8.5 List of Error Codes
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g

Table of Contents