Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 180

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

RY offset/size information
■RY offset/size information (Un\G69424 to Un\G69947)
The start number and the number of points of RY for each station are stored.
Address
Un\G69424 to Un\G69425
Un\G69426 to Un\G69427
Un\G69428 to Un\G69429
Un\G69430 to Un\G69431
Un\G69520 to Un\G69521
Un\G69522 to Un\G69523
Un\G69524 to Un\G69947
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 69424 + (station No.)  4
• Size buffer memory address = 69426 + (station No.)  4
RWw offset/size information
■RWw offset/size information (Un\G69948 to Un\G70471)
The start number and the number of points of RWw for each station are stored.
Address
Un\G69948 to Un\G69949
Un\G69950 to Un\G69951
Un\G69952 to Un\G69953
Un\G69954 to Un\G69955
Un\G70044 to Un\G70045
Un\G70046 to Un\G70047
Un\G70048 to Un\G70471
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 69948 + (station No.)  4
• Size buffer memory address = 69950 + (station No.)  4
RWr offset/size information
■RWr offset/size information (Un\G70472 to Un\G70995)
The start number and the number of points of RWr for each station are stored.
Address
Un\G70472 to Un\G70473
Un\G70474 to Un\G70475
Un\G70476 to Un\G70477
Un\G70478 to Un\G70479
Un\G70568 to Un\G70569
Un\G70570 to Un\G70571
Un\G70572 to Un\G70995
The buffer memory address for the offset and size of each station number can be calculated using the following formulas:
• Offset buffer memory address = 70472 + (station No.)  4
• Size buffer memory address = 70474 + (station No.)  4
APPX
178
Appendix 1 Buffer Memory
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.24 offset
Station No.24 size (in units of words)
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.24 offset
Station No.24 size (in units of words)
System area
Description
Station No.0 offset
Station No.0 size (in units of words)
Station No.1 offset
Station No.1 size (in units of words)
Station No.24 offset
Station No.24 size (in units of words)
System area

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g

Table of Contents