Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 193

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

No.
Name
SB00E8
Station type match status of each station
SB00F0
CPU operating status of each station
SB00F1
CPU operating status of master station
SB0100
CPU moderate/major error status of each
station
SB0101
CPU moderate/major error status of
master station
SB0110
CPU minor error status of each station
SB0111
CPU minor error status of master station
*1 This register is enabled when 'Data link status of own station' (SB0049) is off.
Description
Shows the station type match status of each station.
0: Station types of all stations match
1: Station type mismatch exists.
This relay is turned to "0: Station types of all stations match" when all areas of 'Station type
match status' (SW00E8 to SW00EF) are "0: Station type match".
Depending on the refresh timing, the update of 'Station type match status' (SW00E8 to
SW00EF) may be offset by one sequence scan.
Stores the operating status of the CPU module on each station.
Off: All stations at RUN or PAUSE state
On: Station at STOP state, or station with a moderate/major error exists.
When this relay is turned on, the status of each station can be checked with 'CPU operating
status of each station' (SW00F0 to SW00F7).
Depending on the refresh timing, the update of 'CPU operating status of each station' (SW00F0
to SW00F7) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE TSN Class A remote
station when communicating in multicast mode, "0: RUN, PAUSE" is reflected to the CC-Link IE
TSN Class A remote station.
Stores the operating status of the CPU module on the master station (master operating station).
Off: RUN or PAUSE
On: STOP, or moderate/major error
For local stations, stores the moderate/major error occurrence status of the CPU module on
each station.
For remote stations, stores the moderate/major error occurrence status of each station.
Off: No station with a moderate/major error
On: Station with a moderate/major error exists
When this relay is turned on, the status of each station can be checked with 'CPU moderate/
major error status of each station' (SW0100 to SW0107).
Depending on the refresh timing, the update of 'CPU moderate/major error status of each
station' (SW0100 to SW0107) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE TSN Class A remote
station when communicating in multicast mode, "0: No moderate/major error" is reflected to the
CC-Link IE TSN Class A remote station.
Stores the moderate/major error occurrence status of the CPU module on the master station
(master operating station).
Off: No moderate/major error
On: Moderate/major error
For local stations, stores the minor error occurrence status of the CPU module on each station.
For remote stations, stores the minor error occurrence status of each station.
Off: All stations normal or station with a moderate/major error exists.
On: Station with a minor error exists.
When this relay is turned on, the status of each station can be checked with 'CPU minor error
status of each station' (SW0110 to SW0117).
Depending on the refresh timing, the update of 'CPU minor error status of each station' (SW0110
to SW0117) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE TSN Class A remote
station when communicating in multicast mode, "0: Normal, or a moderate or serious error
occurring" is reflected to the CC-Link IE TSN Class A remote station.
Stores the minor error occurrence status of the CPU module on the master station (master
operating station).
Off: No minor error or a moderate/major error
On: Minor error
Appendix 2 List of Link Special Relay (SB)
A
APPX
191