Error definition and causes
code
1805H
• The total cyclic data size of all device
stations on the CC-Link IE TSN Class A
device side that form a boundary
between CC-Link IE TSN Class B and
CC-Link IE TSN Class A devices
exceeds 2K bytes.
• The total cyclic data size of all device
stations on the CC-Link IE TSN Class A
device side at the boundary between
CC-Link IE TSN Class B and CC-Link IE
TSN Class A exceeds 2K bytes.
1806H
• When "TSN HUB Setting" is set to "Not
to Use TSN HUB", connection of the CC-
Link IE TSN Class B devices in a star
topology has been detected.
• A CC-Link IE TSN Class B device is
connected further on the end side than a
CC-Link IE TSN Class A device.
1810H
A connection failure was detected in the
network.
1811H
A stop error has been detected in the CPU
module.
1830H
Number of reception requests of transient
transmission (link dedicated instruction)
exceeded the upper limit of simultaneously
processable requests.
1845H
Too much processing of transient
transmission (link dedicated instruction)
and cannot perform transient transmission.
18D0H
System error
18D1H
System error
18D2H
System error
1C40H
The station number of the device station to
connect to network in "Network
Configuration Settings" exceeds the total
number of device stations configured.
1C41H
A WDT error of the driver was detected.
1C42H
An unsupported driver was connected.
1C43H
An error occurred in SLMP
communication.
1C44H
System error
1C445
Response timeout was detected in SLMP
communication.
1C46H
System error
1C47H
System error
1C48H
Abnormal response for PDO mapping
setting was received from a device station.
1C49H
A model name mismatch was detected on
reconnection of device station.
8 TROUBLESHOOTING
148
8.5 List of Error Codes
Action
Check the connection and setting on the end side of the station
shown in detailed information 2 based on the error definition and
cause and take the following actions.
• Ensure that the total cyclic data size of all device stations on the
CC-Link IE TSN Class A device side that form a boundary
between CC-Link IE TSN Class B and CC-Link IE TSN Class A
devices does not exceed 2K bytes.
• Do not set the total cyclic data size of all device stations on the
side of the station with a communication speed of 100 Mbps at
the boundary between the station with a communication speed of
1 Gbps and the station with a communication speed of 100 Mbps
to exceed 2K bytes.
• Disconnect the switching hub connected with the CC-Link IE
TSN Class B device.
• Set "TSN HUB Setting" to "Use TSN HUB".
• Connect the CC-Link IE TSN Class A device further on the end
than the CC-Link IE TSN Class B device.
Correct the wiring status.
Check the error of the CPU module in "Module Diagnostics" of the
engineering tool and take action.
Lower the transient transmission usage frequency, and retry the
operation.
Correct the transient transmission (link dedicated instruction)
execution count.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Set the station number of the device station to connect to network
smaller than the total number of device stations.
• When a stop error of the CPU module is detected, check the
error of the CPU module and take corrective action.
• Review the communication period.
• Check for errors in surrounding environment, e.g. noise, and
remove the error factor.
• After the above procedure, switch the power off and then on, or
reset the CPU module."
Please connect a supported driver.
• Review slave object settings.
• Check the manual of the driver.
Please consult your local Mitsubishi representative.
• Review the transient transmission time. It is derived by the
following formula.
• (Transient Transmission Time = Communication Period Interval
Setting - Cyclic Transmission Time - System Reserved Time)"
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
• Check the error according to the error code (SDO Abort Code)
and review the PDO mapping setting.
• Check that CiA402 objects that are set for "(Pr.91) Optional data
monitor : Data type setting 1" to "(Pr.94) Optional data monitor :
Data type setting 4" and "(Pr.591) Optional data monitor : Data
type expansion setting 1 " to "(Pr.594) Optional data monitor :
Data type expansion setting 4" can be monitored."
Connect the device station with the same model name as the
disconnected device station.
Detailed information 1
Detailed information 2
■Own station information
• Intelligent module No.
• Network No.
• Station No.
• IP address
■Target station information
• Network No.
• Station No.
• IP address
■Own station information
• Intelligent module No.
• Network No.
• Station No.
• IP address
■