Structure Of Cc-Link Ie Tsn Class B/A Devices And Ethernet Devices - Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Structure of CC-Link IE TSN Class B/A devices and Ethernet
devices
Connection of Ethernet devices
The following figure shows connection of Ethernet devices to CC-Link IE TSN-compatible devices and a general-purpose
switching hub
No.0
Class B (1 Gbps)
No.1
Class B (1 Gbps)
No.0: Motion module (master station)
No.1: Servo amplifier (remote station)
No.2: Remote I/O module (remote station)
No.3, No.4, No.5:Inverter (remote station)
(1), (2), (3): Ethernet device
 CC-Link IE TSN Class B device area
 CC-Link IE TSN Class A device area
• The Ethernet devices (1 Gbps) can be directly connected to unused ports of the CC-Link IE TSN-compatible
devices without the switching hub.
• The Ethernet devices (100 Mbps) can be connected to the general-purpose switching hub on the boundary
between the CC-Link IE TSN Class B and CC-Link IE TSN Class A areas.
• The Ethernet devices can perform MELSOFT connection and SLMP communications with the master
station. They also can communicate with each other using a protocol that supports each other. For the
maximum number of MELSOFT connection and SLMP communications, refer to the following.
Page 21 Performance Specifications of Ethernet
• Since the CC-Link IE TSN-compatible devices have a smaller memory capacity for packet reception
compared to the switching hub, packets may not reach external devices if the Ethernet devices are directly
connected and high-frequent communications are performed.
• Since Ethernet communications use the transient transmission band on CC-Link IE TSN, the throughput of
the Ethernet communications may decrease when the basic communication cycle is extremely short or
when a large number of packets are communicated. This can be solved by correcting the communication
frequency and the number of connected Ethernet devices.
Ò
No.2
Class B (1 Gbps)
No.3
Class A (100 Mbps)
General-purpose
switching hub
or
No.4
TSN switching hub
Class A (100 Mbps)
(3)
Ó
(1)
No.5
(2)
Class A (100 Mbps)
4 SYSTEM CONFIGURATION
4.5 Connection Examples
4