Rockwell Automation Allen-Bradley ArmorBlock 1732E-IB8M8SOER User Manual page 86

Ethernet/ip dual port 8-point sequence of events input and scheduled output modules
Table of Contents

Advertisement

Appendix A
Module Tags
Table 13 - Configuration Tags – 1732E-OB8M8SR
Tag Name
C.ModuleCfgBits
C.ProgToFaultEn
C.Pt00FaultMode...Pt07FaultMode
C.Pt00FaultValue...Pt07FaultValue
C.Pt00FaultFinalState...Pt07FaultFinalState
C.Pt00ProgMode...Pt07ProgMode
C.Pt00ProgValue...Pt07ProgValue
C.Pt00HoldLastStateDuration...Pt07HoldLastStateDuration BOOL
Table 14 - Input Tags – 1732E-OB8M8SR
Tag Name
I.Fault
I.Data
I.SyncToMaster
I.SyncTimeout
I.LateScheduleCount
I.LostScheduleCount
I.LocalClockOffset
I.OffsetTimeStamp
I.GrandmasterClockID
86
Configuration, Input, Output Tags for 1732E-OB8M8SR
Table 13
to
Table 15
generated in Studio 5000 Logix Designer software when you use your 1732E-
OB8M8SR module.
Type
Description
SINT
Configuration Revision Number.
Selects whether (enabled) or not (disabled) to apply the fault value when the output is already being set
BOOL
to the program value when a Fault (connection timeout) occurs in Program Mode.
The Pt0xFaultMode is used in conjunction with FaultValue to configure the state of output x (that is,
Pt00FaultMode for output 0, Pt01FaultMode for output 1, Pt02FaultMode for output 2, and so on up to
BOOL
Pt07FaultMode for output 7) when a communications fault occurs.
A value of 0 means that, in the case of a communications fault, the value in FaultValue will be used (Off or
On). A value of 1 means that the last state will be held. By default this value is 0.
The Pt0xFaultValue is used in conjunction with FaultMode to configure the state of the output x (that is,
Pt00FaultValue for output 0, Pt01FaultValue for output 1, Pt02FaultValue for output 2 and so on up to
BOOL
Pt07FaultValue for output 7) when a communications fault occurs.
0 = Off (default)
1 = On
If FaultMode is set (Hold Last State) and HoldLastStateDuration[8] is non-zero, this tag determines the
BOOL
final Output state after the configured time out occurs.
The Pt0xProgMode is used in conjunction with ProgValue to configure the state of output 0 when the
controller is in Program mode. A value of 0 means that the ProgValue (Off or On) will be used when the
BOOL
controller is in Program mode. A value of 1 means that the last state will be held. By default this value is
0.
The Pt0xProgValue is used in conjunction with ProgMode to configure the state of output x when the
BOOL
controller is in Program mode. A value of 0 is Off, and a value of 1 is On. By default this value is 0.
If FaultMode is set (Hold Last State), this value determines the length of time the last state is to be held
prior to the FaultFinalState being applied.
Valid values are 0 = Hold Forever, and either 1, 2, 5, or 10 (indicating hold time in seconds). All other
values reserved.
Type
Description
Communication fault – The controller sets this tag to 1 for all 32 bits if a communication fault occurs on the
DINT
module otherwise all bits are zero.
Status of the input point. This data is filtered if the Input Filter feature is used on the module. Thus, an input
change must pass through the filter before it is seen in this tag.
SINT
0 = input is OFF
1 = input is ON
For example, if input 3 is ON, I.Data.3 = 1.
When set, indicates the module has synced to a Valid Time Master.
BOOL
1 = Synchronized
0 = Not synchronized
BOOL
Indicates a Valid local CIP Sync Timemaster has since timed out.
Indicates that a schedule request arrived at the module after the schedule time. The counter rolls over to 1 every
INT
65,535 late updates.
Indicates that a schedule sequence number has been skipped, thus a schedule request has been lost. The
INT
counter rolls over to 1 every 65535 lost updates.
The offset from the local clock to the system time. This value is useful for detecting steps in time.
DINT[2]
This value updates when a PTP update is received.
The time when the PTP message was received to cause the Local Clock Offset to update.
DINT[2]
This value is initially zero. The first timestamp occurs when the module synchronizes with the Grandmaster clock.
DINT[2]
The ID number of the Grandmaster clock that the module is synchronized to.
Rockwell Automation Publication 1732E-UM003D-EN-E - November 2021
describe the configuration, input, and output tags