Appendix B
Data Tables
90
Table 17 - Configuration Assembly Instance 124 Data Structure (Configuration Header)
Configuration Byte
Bit 7
0
Reserved (Ignored)
1
Reserved (Ignored)
2
Reserved (Ignored)
3
Reserved (Ignored)
CRN
Configuration Revision Number
Table 18 - Assembly Instance 4 Data Structure
Produced Byte
Bit 7
0
In 7
Table 19 - Assembly Instance 34 Data Structure
Consumed Byte
Bit 7
0
Out 7
Table 20 - Assembly Instance 111 Data Structure
Consumed
Bit 7
Byte
4
Group 0 Input OFF_ON Delay Filter (Low Byte)
5
Group 0 Input OFF_ON Delay Filter (High Byte)
6
Group 0 Input ON_OFF Delay Filter (Low Byte)
7
Group 0 Input ON_OFF Delay Filter (High Byte)
8
Reserved (Ignored)
Capture
9
OffOn7
Capture
10
OnOff7
11
Reserved (Ignored)
MasterSyncEnable – This is a PTP enable bit which indicates if the module is expected to synch to a
master clock. If not enabled (0), then the Module LED does not flash green if not synched to a master
clock. Disabling the bit does not prevent the module from synchronizing to a master clock.
LatchEvents – When set, latches events means that an event is not overwritten until acknowledged. In
Per Point mode, a sequence of events of LO, HI, LO will cause the first LO and HI transitions to be
recorded and the final LO to be ignored. All subsequent transitions on that point will be ignored until
Where:
acknowledged/reset. If the bit is not set, the new LO will overwrite the first LO event immediately, even
if the controller has yet to extract that data. In FIFO mode, when set events will not be erased from the
FIFO until read.
CaptureOffOn – Enables capturing Off to On events on a per point basis. If cleared, that point will not
record Off to On events. Useful to not use up buffer space on events user does not care about.
CaptureOnOff – Enables capturing On to Off events on a per point basis. If cleared, that point will not
record On to Off events. Useful to not use up buffer space on events user does not care about.
Rockwell Automation Publication 1732E-UM003D-EN-E - November 2021
Bit 6
Bit 5
Bit 4
Bit 6
Bit 5
Bit 4
In 6
In 5
In 4
Bit 6
Bit 5
Bit 4
Out 6
Out 5
Out 4
Bit 6
Bit 5
Bit 4
Capture
Capture
Capture
OffOn6
OffOn5
OffOn4
Capture
Capture
Capture
OnOff7
OnOff7
OnOff7
Bit 3
Bit 2
Bit 1
Bit 3
Bit 2
Bit 1
In 3
In 2
In 1
Bit 3
Bit 2
Bit 1
Out 3
Out 2
Out 1
Bit 3
Bit 2
Bit 1
Bit 0
Master
Latch
Sync
Events
Enable
Capture
Capture
Capture
Capture
OffOn3
OffOn2
OffOn1
OffOn0
Capture
Capture
Capture
Capture
OnOff7
OnOff7
OnOff7
OnOff7
Bit 0
CRN
Bit 0
In 0
Bit 0
Out 0