Introduction
Determine Module
Compatibility
Operational Modes
Specific Features of the 1732E-OB8M8SR
Scheduled Output Module
This chapter describes the features specific to the 1732E-OB8M8SR Scheduled
Output module.
Topic
Determine Module Compatibility
Operational Modes
Time-Scheduled Output Control
Configurable Point-Level Output Fault States
Output State
These features can be configured through the Studio 5000 Logix Designer
software.
The Scheduled Output module 1732E-OB8M8SR serves to provide high speed
scheduling of every output signal based on time scheduling. Time scheduling
is obtained via CIP synchronization (CIP Sync).
All outputs can be individually scheduled. Users shall be able to define the
number of outputs to be used for scheduling purposes, leaving the other
outputs for use as normal outputs.
When designing a system using this module, you must consider:
•
The voltage necessary for your application
•
Whether you need a solid state device
•
Current leakage
•
If your application should use sinking or sourcing wiring
For more information on compatibility of other Rockwell Automation
products to modules, visit the Product Compatibility and Download Center
page at rok.auto/pcdc.
Table 7 - Module Compatibility
Operational Mode
Normal Output
Scheduled Output without use of MAOC
Scheduled Output with use of MAOC
The 1732E-OB8M8SR output module has two modes of handling the individual
output points:
Rockwell Automation Publication 1732E-UM003D-EN-E - November 2021
Page
55
55
56
56
57
Required version of
Studio 5000 Logix Designer Configuration to use
Timestamp = none
Version 18 or later
MAOC Support = No
Timestamp = none
Version 18 or later
MAOC Support = No
Timestamp = Per Point
Version 21 or later
MAOC Support = Yes
9
Chapter