Appendix B
Data Tables
94
Table 23 - Consumed Assembly Instance 159 Data Structure
Consumed
Bit 7
Bit 6
Byte
0...3
Event Ack (32 Bits)
NewData
NewData
4
Ack7
Ack7
5
Point to Retrieve
6
Reserved (Ignore)
FIFO Mode
EventAck – The controller writes back the EventNumber read to transition buffers. All events with
EventNumbers less than or equal to the EventAck will be acknowledged. If the RetreiveByPoint bit is set
the PointToRetrieve attribute must also be used to specify the point to retrieve next.
NewDataAck – Forces NewData bits clear even if all the timestamps for that point have not been
acknowledged. Also clears the EventOv bits.
PointToRetrieve – When RetrieveByPoint is set, determines point requested for events to be returned.
Allows a user to query events in the sequence they happened by point instead of the overall sequence
the events occurred.
Where:
RetrieveByPoint – Changes retrieval mechanism from sequential (when 0) to retrieving events on a per
point basis according to value set in PointToRetrieve field.
Per Point Mode
EventAck – Is a 0 or 1 to indicate acknowledging an OnOff or OffOn event respectively, or a 2 to
acknowledge both.
NewDataAck – Acknowledges the corresponding inputs timestamp and clears its NewData and EventOv
bits.
PointToRetrieve – Not used.
RetrieveByPoint – Not used.
Reset Events – When transitioned from 0 to 1, erases all recorded time stamped events.
Table 24 - Configuration Assembly Instance 163 Data Structure
Consumed
Bit 7
Bit 6
Byte
4
Group 0 Input OFF_ON Delay Filter (Low Byte)
5
Group 0 Input OFF_ON Delay Filter (High Byte)
6
Group 0 Input ON_OFF Delay Filter (Low Byte)
7
Group 0 Input ON_OFF Delay Filter (High Byte)
8
Reserved (Ignored)
9
Reserved (Ignored)
FA_G0 = Fault Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
IA_G0 = Idle Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
Where:
FV_G0 = Fault Value Group 0 (0 = OFF;1 = ON)
IV_G0 = Idle Value Group 0 (0 = OFF;1 = ON)
Rockwell Automation Publication 1732E-UM003D-EN-E - November 2021
Bit 5
Bit 4
Bit 3
NewData
NewData
NewData
Ack7
Ack7
Ack7
Bit 5
Bit 4
Bit 3
IV_G0
Bit 2
Bit 1
Bit 0
NewData
NewData
NewData
Ack7
Ack7
Ack7
Retrieve by
Reset
Point
Events
Bit 2
Bit 1
Bit 0
IA_G0
FV_G0
FA_G0