7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Requirements conditions of SEMI-F47 standard
Table 7.2 shows the permissible time of instantaneous power failure for instantaneous power failure of
SEMI-F47 standard.
(3) Calculation of tolerance against instantaneous power failure
Table 7.3 shows tolerance against instantaneous power failure when instantaneous power failure
voltage is "rated voltage × 50%" and instantaneous power failure time is 200 ms.
Table 7.2 Requirements conditions of SEMI-F47 standard
Instantaneous power
failure voltage
Rated voltage × 80%
Rated voltage × 70%
Rated voltage × 50%
Table 7.3 Tolerance against instantaneous power failure
(instantaneous power failure voltage = rated voltage × 50%,
instantaneous power failure time = 200 ms)
Servo amplifier model
MR-J4-10TM
MR-J4-20TM
MR-J4-40TM
MR-J4-60TM
MR-J4-70TM
MR-J4-100TM
MR-J4-200TM
MR-J4-350TM
MR-J4-500TM
MR-J4-700TM
MR-J4-11KTM
MR-J4-15KTM
MR-J4-22KTM
MR-J4-60TM4
MR-J4-100TM4
MR-J4-200TM4
MR-J4-350TM4
MR-J4-500TM4
MR-J4-700TM4
MR-J4-11KTM4
MR-J4-15KTM4
MR-J4-22KTM4
Permissible time of
instantaneous power
failure [s]
1
0.5
0.2
Instantaneous maximum
output [W]
350
700
1400
2100
2625
3000
5400
10500
15000
21000
40000
50000
56000
1900
3500
5400
10500
15000
21000
40000
50000
56000
7 - 31
Tolerance against
instantaneous
power failure [W]
(voltage drop between lines)
250
420
630
410
1150
1190
2040
2600
4100
5900
2600
3500
4300
190
200
350
730
890
1500
2400
3200
4200