Sub-Bus Hub Module
The G3 HUB module allows for branch distribution from the I/O side of the G3 System and can be integrated
into the existing G3 Series Sub-Bus configuration. Auto Addressing allows for trouble free set up and
configuration. Input, Output, as well as Valve manifolds can be attached to the available four Branches on a
HUB module. Each G3 System can support up to two HUB modules, allowing for maximum flexibility. The
HUB module is transparent to the I/O side of the G3 and does not reserve one of the potential sixteen
positions.
Used when distributing the Sub-Bus to another assembly.
SUB-BUS OUT - 5 pin M12 female communication connector.
Used to distribute the Sub-Bus to the next Sub-Bus assembly.
o
Carries 24 VDC power (up to 3A) for electronics of the next module.
o
Cannot connect a Hub to a branch of another Hub
Each branch of the Hub can accommodate a sub-bus cable length of 30 meters