RTD Module / Alarm Settings:
Allows the Low and High alarms of each RTD Input channel to be set. This parameter generates a visual and logical
(bit) when set value is achieved.
ALARM
SETTINGS
NOTE!
G3 Series PROFIBUS-DP
SET ALARM
CHANNEL CH0
SET ALRM CH1
LO = -200.0 C
SET ALRM CH1
LO = -200.0 C
ACCEPT
50.0 C
Y
N
When Alarm values are set to maximum/minimum values, the alarm function is
disabled.
Factory default settings for all alarms are disabled.
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
A)
Press the SET button to enter the
Alarm Settings sub-menu.
B)
Press the NEXT button to scroll
through the RTD Input channels.
C)
Press the SET button to enter the
alarm setting for the selected Input
channel.
D)
Press the NEXT button to select the
Lo or High setting for the selected
channel.
E)
Press the SET button to select the
change process for the chosen alarm.
The first digit/sign will be
highlighted.
Press the NEXT button to choose the
F)
value, or the SET button to select
and move to the next digit.
G) Press the NEXT button to choose "Y"
or "N" Select. Then press the SET
Button to Accept.