5.11

Diagnostics

DIAGNOSTICS
SET SELF TEST
UNSW POWER
24 VOLTS
NETWORK
ERRORS
CURRENT NODE
EVENT - #
SHOW LOGGED
NODE EVENTS
CURRENT
SUBBUS
SHOW LOGGED
SUBBUS ERRORS
FIRMWARE REV.
1.024
BOOTCODE REV.
1.09
PART NUMBER
240-239
NOTE!
G3 Series PROFIBUS-DP
The UNSW POWER screen indicates the voltage level present on the UNSW
(Node & Input) power pins (Pin No. 2 and 4) of the main power connector.
A voltage level less than 19 volts will generate an error screen and an
associated diagnostic bit (see 'Diagnostic' section for more details).
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
1.
All diagnostic information is read only
2.
Press the SET button to enter DIAGNOSTICS sub-
menu.
3.
Press the NEXT button to scroll through the main
diagnostic menu choices.
a.
SET SELF TEST
- Please see following page for description
b.
UNSW POWER
- Displays voltage level of unswitched
power (Node & Inputs)
c.
NETWORK ERRORS - ERROR CODE
- Displays fieldbus network errors
d.
CURRENT COMM. EVENT NUMBER
- Displays node event number
e.
SHOW LOGGED COMM. EVENTS
- Displays log of node events
f.
CURRENT SUBBUS ERROR
- Displays sub bus errors
g.
SHOW LOGGED SUBBUS ERRORS
- Displays log of sub bus errors
h.
FIRMWARE REV.
- For service personnel
i.
BOOTCODE REV.
-For service personnel
j.
PART NUMBER
- Displays replacement part number of
module
07/2020
5-37

Advertisement

Table of Contents
loading

Table of Contents