Analog Module / Self Test Mode - Emerson Aventics G3 Series Technical Manual

Profibus dp-v0 dp-v1
Hide thumbs Also See for Aventics G3 Series:
Table of Contents

Advertisement

10.3 Analog Module / Self Test Mode

Self test mode is an internal diagnostic tool that can be enabled on the analog module using the graphic display.
This tool allows the user to confirm that all of the outputs on the module are fully functional without needing a
network connection or controller. The test will cycle the analog outputs. Starting with Output 0 it will increment the
analog signal at 10% intervals; once it has reached 100% it will test the next available output. The self-test will
continue to run until it is turned off by pressing the SET button.
To use the Self Test Mode, the user must first set some initial conditions. Follow these steps to initiate the self-test
mode.
1)
Disconnect Air and Communication from the manifold!
2)
Starting at the Home Screen, navigate the menus by selecting the NEXT button until the SELF-TEST
menu is shown.
3)
Select the SET button to access the SELF-TEST menu
4)
A message will appear: DISCONNECT AIR HOLD SET BUTTON
5)
Hold the SET button down for approximately 10 seconds to enable the test. The Display will flash the
above message while the button is pushed.
6)
When the display stops flashing, the self-test mode will be running
7)
Push or hold the NEXT button to cycle through the outputs. Holding the NEXT button will allow the
analog outputs to cycle through the 10% intervals automatically. Pushing the NEXT button will allow
the outputs to manually step through each 10% interval.
8)
Releasing the NEXT button will keep the output in its current state.
9)
The self-test mode can only be disabled by pushing the SET button
G3 Series PROFIBUS-DP
AO0
AO1
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
SET SELF TEST
DISCONNECT AIR
HOLD SET BUTTON
HOLD FOR 10 SECONDS TO
INITIATE
07/2020
10-91

Advertisement

Table of Contents
loading

Table of Contents