Error/Event Messages
The following are error messages that are displayed when specific faults/events occur during operation:
MISSING MODULE
NUMBER XX
SUB-BUS
SHORT CIRCUIT
Connector Pin Out
5
FEMALE
PIN 1 = Shield
PIN 2 = V+
PIN 3 = V-
PIN 4 = CAN_H
PIN 5 = CAN_L
NOTE!
G3 Series PROFIBUS-DP
Length of molded or field wired Sub-Bus Branch cables should not exceed the maximum
length of 30 meters per Sub-Bus Branch communication link.
The molded cable assemblies and bulk cable are the only approved cables for the G3 Sub-Bus
and Branch Link. Please refer to page 7-50, for Sub-Bus cable and connectors options. See
Technical Document on page 7-51 for proper installation and wiring of field wire-able
connectors.
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
Displayed when a Sub-Bus module that had been
previously installed becomes absent from the
configuration
Displayed when a Sub-Bus power short circuit
condition is detected
07/2020
11-110