Emerson Aventics G3 Series Technical Manual page 60

Profibus dp-v0 dp-v1
Hide thumbs Also See for Aventics G3 Series:
Table of Contents

Advertisement

Intrinsically safe [Ex ia] NAMUR Compatible Input Module
One Digital Input per Connector – M12 Female
Input module is for use with NAMUR certified intrinsically safe (IS) sensors. The module can be placed in any G3 I/O
position available but must be used in conjunction with appropriate clips with partition plates (see picture on page 8-62).
This module is for use with (IS) sensors (certified to EN 60947-5-6) where the sensor is placed within the hazardous area,
(e.g. ATEX 0-20, 1-21, and 2-22). This [Ex ia] module is part of the G3 electronics platform, which is designed to reside
outside of the hazardous environment or in Zone 2-22, inside of a cabinet with appropriate ingress protection. The
partition plate clips, used between standard G3 modules and
[Ex ia] modules, are required to maintain ATEX approval. The 8.2 V sensor supply for each input connector is short circuit
protected.
Part Numbers and Mapping
Module
I/O Type
Part No.
240-320
NAMUR
BYTE
Bit 7
X
Input
(Required)
7
Conn. H
X
SC
Status
Conn. H
X + 1
Open
Status
G3 Series PROFIBUS-DP
Short Circuit /Open Circuit
Protection
YES - Visual
Input Mapping
Bit 6
Bit 5
Input
Input
6
5
Diagnostic Telegram
Conn. G
Conn. F
Conn. E
SC
SC
Status
Status
Status
Conn. G
Conn. F
Conn. E
Open
Open
Status
Status
Status
TDG3PTTM1-11EN
Subject to change without notice
www.asco.com
Technical Manual
TM
Short Circuit /Open Circuit
Present Status Bits
YES - Optional
Bit 4
Bit 3
Bit 2
Input
Input
Input
4
3
Conn. D
Conn. C
SC
SC
Status
Status
Conn. D
Conn. C
Open
Open
Open
Status
Status
07/2020
Input Points
8
Bit 1
Bit 0
Input
Input
2
1
0
Conn. B
Conn. A
SC
SC
SC
Status
Status
Conn. B
Conn. A
Open
Open
Status
Status
8-60