Single-Phase 3-Wire 2-Currents: 1P-3W2I; Two-Phase 3-Wire (Two-Phase From A Mid-Tap Transformer): 2P-3W2I - AEMC PEL 52 User Manual

Power & energy logger
Hide thumbs Also See for PEL 52:
Table of Contents

Advertisement

4.1.2 Single-Phase 3-wire 2-currents: 1P-3W2I

For single-phase 3-wire measurements with 2 current sensors:
Connect the N measuring lead to the neutral conductor.
Connect the V1 measuring lead to the L1-I1 phase conductor.
Connect the V2 measuring lead to the L1-I2 phase conductor.
Connect the I1 current sensor to the L1-I1 phase conductor.
Connect the I2 current sensor to the L1-I2 phase conductor.
4.1.3 Two-Phase 3-wire (two-phase from a mid-tap
transformer): 2P-3W2I
For two-phase 3-wire measurements with 2 current sensors:
Connect the N measuring lead to the neutral conductor.
Connect the V1 measuring lead to the L1 phase conductor.
Connect the V2 measuring lead to the L2 phase conductor.
Connect the I1 current sensor to the L1 phase conductor.
Connect the I2 current sensor to the L2 phase conductor.
Power & Energy Logger Model PEL 52 - User Manual
L1
N
I2
V2
600 V
max
V1
N
Figure 24
L2
L1
N
V2
I2
600 V
max
V1
N
Figure 25
L1-I2
L1-I1
N
I1
600 V CAT III
L1
N
L2
I1
600 V CAT III
33