Crest factor:
(2.8 to 360) A on the 300 A range.
■
(1.7 to 3600) A on the 3000 A range.
■
AmpFlex
and MiniFlex
®
Like all Rogowski sensors, the output voltage of AmpFlex
proportionate to the frequency. High current at high frequency can saturate the
current input of devices.
This requirement does not consider the bandwidth limitation of the device, which
can lead to other errors.
6.3 VARIATION IN THE FIELD OF USE
6.3.1 General
Internal clock drift: ± 5 ppm/year at (77 ± 5.4) °F (25 ± 3) °C
6.3.2 Temperature
V1, V2: 27.78 ppm/°F (50 ppm/°C) typical
I1, I2: 83.33 ppm/°F (150 ppm/°C) typical, for 5 % I
Internal clock: 5.56 ppm/°F (10 ppm/°C)
6.3.3 Humidity
Range of influence: (30 to 75) % RH / 85 % RH at 73.4 °F (23 °C) excluding
V1, V2: ± 0.05 % typical
I1, I2 (1 % I
≤ I ≤ 10 % I
nom
(10 % I
< I ≤ 120 % I
nom
6.3.4 Continous Component
Range of influence: ± 100 Vdc
Quantities influenced: V1, V2
Rejection: > 60 dB
6.3.5 Frequency
Range of influence: (45 to 65) Hz, - 60 ° ≤ φ ≤ +60 °
Quantities influenced: V1, V2, I1, I2, P1, P2
Influence: 0.1 %/Hz
56
limitation
®
condensation
): 0.1 % typical
nom
): 0.05 % typical
nom
Power & Energy Logger Model PEL 52 - User Manual
and MiniFlex
®
< I < 120 % I
nom
nom
is
®