6-9

Communications Setting Level

psel
u-no
bps
len
sbit
prty
sdwt
• Each parameter is enabled when the power is reset.
• Match the communications specifications of the E5@C and the host computer. If multiple
devices are connected, ensure that the communications specifications for all devices in
Function
the system (except the Communications unit number) are the same.
Protocol setting
Setting
Communications
Unit No.
Communications
baud rate
Communications
data length
Stop bits
Communications
parity
Send data wait
time
*
Related Parameter
See
See
Communications Writing (Adjustment Level): Page 6-21
E5@C Digital Temperature Controllers User's Manual (H174)
Protocol Setting
Communications Unit No.
Communications Baud Rate
Communications Data Length
Communications Stop Bits
Communications Parity
Send Data Wait Time
Item
Display
psel
u-no
bps
len
sbit
prty
sdwt
Writing with communications is enabled if you set the Protocol Setting parameter to component
communications, Host Link (FINS), MC protocol (format 4), or dedicated protocol (format 4).
Communications must be supported.
CompoWay/F must be selected as the protocol.
CompoWay/F must be selected as the protocol.
CompoWay/F or Modbus must be selected as the
protocol.
Set values
cwf/
CompoWay/F
mod
Modbus
cmp
Component communications
fins
Host Link (FINS)
mcp4
MC Protocol (format 4)
fxp4
Dedicated protocol (format 4)
0 to 99
0 to 99
9.6/19.2/38.4/57.6
9.6/19.2/38. 4/57.6 (kbps)
(Kbps)
7 or 8 bits
7 or 8 bits
1 or 2 bits
1 or 2 bits
none/eVen/odd
None, Even, Odd
0 to 99
0 to 99 (ms)
6 Parameters
Settings
Default
cwf
1
9.6
7
2
eVen
20