5 Advanced Operations
Parameter name
Auxiliary Output 1
Assignment
Auxiliary Output 2
Assignment
Auxiliary Output 3
Assignment
Auxiliary Output 4
Assignment
*1 If the Digital Controller is equipped with HB/HS alarm detection, it is set by default to ha (Heater Alarm). If
the Program Pattern parameter is changed to a setting other than OFF, the Auxiliary Output 1 Assignment
parameter is set as the program end output.
*2 When heating/cooling control is used on the E5GC, auxiliary output 1 is the control output for cooling.
• The heating/cooling operation of the control outputs will switch when the Direct/Reverse
Operation parameter is set to direct operation.
• When DRS (Invert Direct/Reverse Operation) is set for an Event Input Assignment 1 to 6
parameter, control will start with the opposite of the setting of the Direct/Reverse Operation
parameter when the event input turns ON. When the event input turns OFF, control will return to
operation according to the setting of the Direct/Reverse Operation parameter. For details on event
inputs and control combined with the Direct/Reverse Operation parameter, refer to Control by
Inverting Direct/Reverse Operation on page 5-13.
• If heating/cooling control is selected, also set the Dead Band, Proportional Band (Cooling),
Integral Time (Cooling), Derivative Time (Cooling), and Heating/Cooling Tuning Method
parameters.
Dead Band
• For heating/cooling control, the dead band is set with the set point as its center. The dead band
width is the set value of the Dead Band parameter (Adjustment Level). Setting a negative value
produces an overlapping band.
• If an overlapping band is set, the bumpless function may not operate when switching between
manual operation and automatic operation.
• The default is 0.0 EU for Digital Controllers with Temperature Inputs and 0.00% FS for Digital
Controllers with Analog Inputs.
Output
Heating
side
0
5 - 8
Without control output 2
Display
Standard
*1
sub1
Alarm 1
sub2
Alarm 2
sub3
Alarm 3
sub4
Alarm 4
Dead band: Dead band
width = A positive value
Cooling
side
PV
Set point
Heating/cooling
*1
Alarm 1
Alarm 1
Alarm 2
Alarm 2
Alarm 3
Alarm 3
Control output
Alarm 4
(cooing)
Overlapping dead band: Dead band
Output
width = A negative value
Cooling
Heating
side
side
PV
0
Set point
E5@C Digital Temperature Controllers User's Manual (H174)
With control output 2
Standard
Heating/cooling
*1
*1
Alarm 1
Alarm 2
Alarm 3
Alarm 4