6 Parameters
rsrt
This parameter sets a factor to apply to the remote SP input to compensate it. The resulting
value is displayed as the remote SP input value and used in control.
Function
Setting
Related Parameters
See
See
ST (self-tuning) (Initial Setting Level): Page 6-45
Remote SP Enable (Advanced Function Setting Level): Page 6-84
p
i
d
These parameters set PID control constants. PID constants are automatically set when AT or ST is exe-
cuted.
P
action:
Setting
I
action:
D
action:
6 - 28
Remote SP Input Slope Coefficient
000
Setting range
0.001 to 9.999
Proportional Band
Integral Time
Derivative Time
Refers to control in which the MV is proportional to the deviation (control error).
Refers to a control action that is proportional to the time integral of the deviation.
With proportional control, there is normally an offset (control error). Proportional
action is thus used in combination with integral action. As time passes, this control
error disappears, and the control temperature (process value) comes to agree
with the set point.
Refers to a control action that is proportional to the time derivative of the control
error. The proportional control and integral control correct for errors in the control
result, and thus the control system is late in responding to sudden changes in
temperature. The derivative action increases the MV in proportion to the slope of
the change in the temperature as a corrective action.
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
The Remote SP Enable parameter must be set to
ON (default: OFF).
Default
1.000
The control must be set to 2-PID control.
E5@C Digital Temperature Controllers User's Manual (H174)