6 Parameters
rs-t
This parameter sets the input type for the remote SP.
Function
4-20: 4 to 20mA
Setting
0-20: 0 to 20mA
1-5v: 1 to 5V
0-5v: 0 to 5V
0-10: 0 to 10V
Related Parameters
See
See
ST (self-tuning) (Initial Setting Level): Page 6-45
rspu
This parameter is set to ON to enable setting SP Mode. You can set the SP Mode parameter
to LSP to select a local SP or to RSP to select a remote SP. If this parameter is set to OFF,
only a local SP can be used.
Function
Setting
Related Parameters
See
See
SP Mode (Adjustment Level): Page 6-21
ST (self-tuning) (Initial Setting Level): Page 6-45
6 - 84
000
Remote SP Input
Setting range
000
Remote SP Enable
Setting range
on: Enabled or off: Disabled
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
Default
4-20
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
Default
off
E5@C Digital Temperature Controllers User's Manual (H174)