Limit, Set Point Lower Limit, or Temperature Unit. If the Simple Transfer MV (Heating) or Simple
Transfer MV (Cooling) is selected, the Simple Transfer Output 1 Lower Limit and Simple Transfer
Output 1 Upper Limit parameters will be initialized to 100.0 and 0.0, respectively, when a switch is
made between standard control and heating/cooling control using the Standard or
Heating/Cooling parameter.
• The output current when the Simple Transfer Output 1 Signal parameter is set to 4 to 20 mA, the
Simple Transfer Output 1 Upper Limit parameter is set to 90.0, and the Simple Transfer Output 1
Lower Limit parameter is set to 10.0 is shown in the following graph.
• For scaling from 0.0% to 100.0%, the output for −5.0 to 0.0 will be the same value as for 0.0%, and
the output for 100.0 to 105.0 will be the same value as for 100.0%
5 - 40
Output current (mA)
20
4
0
10
90
Simple Transfer
Simple Transfer
Output 1 Upper Limit
Output 1 Lower Limit
(The above graph is for when the simple transfer
output 1 signal is set to 4 to 20 mA.)
MV (%)
100
E5@C Digital Temperature Controllers User's Manual (H174)