5 Advanced Operations
Setting Change Protect
This protect level restricts key operations
wtpt
off
PF Key Protect
This protect level enables or disables PF Key operations.
pfpt
off
5-7-2

Entering the Password to Move to the Protect Level

• The Protect Level can be moved to only by displaying the password display and entering the correct
password. (The user can set any password in the Password to Move to Protect Level parameter.) If no
password is set (i.e., if the password is set to 0 in the Password to Move to Protect Level parameter),
the password input display to move to the Protect Level will not be displayed and the Protect Level
can be moved to directly.
Move to the Protect Level and set the password.
Example password: 1234
Operating Procedure
Password Not Yet Set
1
Press the O and M Keys simultaneously for at least 3 sec-
onds (default) in the Operation Level.
If a password is not set, the Protect Level will be entered and oapt
(Operation/Adjustment Protect) will be displayed.
2
Press the M Key several times in the Protect Level to display
prlp (Password to Move to Protect Level).
3
Press the O and U Keys simultaneously and set the value to
1234. (This enters the password.)
To prevent setting the password incorrectly, the U and O Keys or
D and O Keys must be pressed simultaneously to set the
password.
The key pressing time can be changed in prlt (Move to Protect Level Time) in the Advanced
*1
Function Setting Level. (Setting range: 1 to 30 seconds, Default: 3 seconds)
5 - 20
Set value
OFF
Settings can be changed using key operations.
ON
Settings cannot be changed using key operations. (The protect level set-
tings, however, can be changed.)
• The default is OFF.
• The setting change protection indicator (
parameter is set to ON.
Set value
OFF
PF Key enabled.
ON
PF Key disabled (Operation as function key prohibited).
• The default is OFF.
Description
) will light when the Setting Change Protect
Description
*1
E5@C Digital Temperature Controllers User's Manual (H174)
000
Protect Level
oapt
Operation/
Adjustment
0
Protect
prlp
Password to
Move to
0
Protect Level
prlp
1234