Omron E5GC User Manual page 354

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

7 User Calibration
t -6
2988
bia5
35b8
str
no
7 - 6
6. When the M Key is pressed, the status changes as shown to the left.
Set the STV to −6 mV.
Allow the count value on the No. 2 display to fully stabilize, then press the D Key
to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
7. When the M Key is pressed, the status changes as shown to the left.
8. Change the wiring as follows:
E5CC, E5CC-U, E5EC, E5AC, or E5DC
Open in non-connected state
STV
DMM
Connect.
Zero controller
OUTPUT INPUT
Disconnect the STV to enable the thermocouple of the cold junction compensator.
When doing this, be sure to disconnect the wiring on the STV side.
9. Allow the count value on the No. 2 display to fully stabilize, then press the D Key
to temporarily register the calibration settings.
10. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and wait
two seconds or press the M Key. This stores the temporarily registered calibration
data to non-volatile memory. To cancel the saving of temporarily registered
calibration data to non-volatile memory, press the M Key (while no is displayed in
the No. 2 display) without pressing the U Key.
11. The calibration mode is ended by turning the power OFF.
For Digital Controllers that have a transfer output, you can continue by calibrating
the transfer output. For detailed setting methods, refer to 7-6 Calibrating the
Transfer Output.
E5@C-B or E5GC
Open in non-connected state
STV
DMM
Connect.
+
Zero controller
OUTPUT
Compensating conductor of currently selected
thermocouple
Use K thermocouple compensating conductor for E, R, S, B,
W, and PLII thermocouples and for an infrared temperature
sensor.
E5@C Digital Temperature Controllers User's Manual (H174)
Relay
terminal block
+
INPUT

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ccE5ecE5acE5dcE5 c seriesE5cc-u ... Show all

Table of Contents