Omron E5GC User Manual page 158

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

4 Basic Operation
Set
value
4
5
6
7
8
9
10
11
12
13
14
15
16
4 - 32
Alarm type
When alarm value
X is positive
Upper- and
ON
lower-limit range*1
OFF
Upper- and
ON
lower-limit with
OFF
standby
*5
sequence*1
Upper-limit with
ON
standby sequence
OFF
Lower-limit with
ON
standby sequence
OFF
Absolute-value
ON
upper-limit
OFF
Absolute-value
ON
lower-limit
OFF
Absolute-value
ON
upper-limit with
OFF
standby sequence
Absolute-value
ON
lower-limit with
OFF
standby sequence
LBA (alarm 1 type
only)
PV change rate
alarm
SP absolute-value
ON
upper-limit alarm
OFF
SP absolute-value
ON
lower-limit alarm
OFF
MV absolute-value
Standard Control
upper-limit alarm*9
ON
OFF
Heating/Cooling
Control (Heating
MV)
ON
OFF
Alarm output operation
When alarm value
X is negative
*3
L
H
PV
SP
*4
L
H
PV
SP
X
X
ON
PV
OFF
SP
SP
X
X
ON
PV
OFF
SP
SP
X
X
ON
PV
OFF
0
0
X
X
ON
PV
OFF
0
0
X
X
ON
PV
OFF
0
0
X
X
ON
PV
OFF
0
0
X
X
ON
SP
OFF
0
0
X
X
ON
SP
OFF
0
0
Standard Control
X
X
ON
MV
OFF
0
0
Heating/Cooling
Control (Heating
MV)
X
Always ON
MV
0
E5@C Digital Temperature Controllers User's Manual (H174)
Description of function
Set the upward deviation in
the set point for the alarm
upper limit (H) and the
lower deviation in the set
point for the alarm lower
limit (L). The alarm is ON
when the PV is inside this
deviation range.
A standby sequence is
added to the upper- and
lower-limit alarm (1).*6
A standby sequence is
added to the upper-limit
PV
alarm (2).*6
A standby sequence is
added to the lower-limit
PV
alarm (3).*6
The alarm will turn ON if the
process value is larger than
PV
the alarm value (X)
regardless of the set point.
The alarm will turn ON if the
process value is smaller
PV
than the alarm value (X)
regardless of the set point.
A standby sequence is
added to the absolute-value
PV
upper-limit alarm (8).*6
A standby sequence is
added to the absolute-value
PV
lower-limit alarm (9).*6
*7
*8
This alarm type turns ON
the alarm when the set
SP
point (SP) is higher than the
alarm value (X).
This alarm type turns ON
the alarm when the set
SP
point (SP) is lower than the
alarm value (X).
This alarm type turns ON
the alarm when the
manipulated variable (MV)
MV
is higher than the alarm
value (X).