Omron E5GC User Manual page 156

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

4 Basic Operation
When P (Proportional Band) Is Adjusted
Increased
Decreased
When I (Integral Time) Is Adjusted
Increased
Decreased
When D (Derivative Time) Is Adjusted
Increased
Decreased
4 - 30
Set
value
Set
value
Set
value
Set
value
Set
value
Set
value
The curve rises gradually, and a long stabilization time
is created, but overshooting is prevented.
Overshooting and hunting occur, but the set value is
quickly reached and the temperature stabilizes.
It takes a long time to reach the set point.
It takes time to achieve a stable state, but overshooting,
undershooting, and hunting are reduced.
Overshooting and undershooting occur.
Hunting occurs.
The Digital Controller starts up faster.
Overshooting, undershooting, and stabilization times
are reduced, but fine hunting occurs on changes in the
curve itself.
Overshooting and undershooting increase, and it takes
time to return to the set point.
E5@C Digital Temperature Controllers User's Manual (H174)

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ccE5ecE5acE5dcE5 c seriesE5cc-u ... Show all