Omron E5GC User Manual page 358

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

7 User Calibration
str
no
7 - 10
7. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and wait two seconds or
press the M Key. This stores the temporarily registered calibration data to non-volatile
memory.
To cancel the saving of temporarily registered calibration data to non-volatile memory, press
the M Key (while no is displayed in the No. 2 display) without pressing the U Key.
8. The calibration mode is ended by turning the power OFF.
For Digital Controllers that have a transfer output, you can continue by calibrating the transfer
output. For detailed setting methods, refer to 7-6 Calibrating the Transfer Output.
E5@C Digital Temperature Controllers User's Manual (H174)

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ccE5ecE5acE5dcE5 c seriesE5cc-u ... Show all

Table of Contents