Omron E5GC User Manual page 360

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

7 User Calibration
• Input type 27 or
28:
1V 1
5ac0
• Input type 29:
2V 1
4ad9
• Input type 30:
t -6
2988
str
no
7 - 12
6. When the M Key is pressed, the status changes as shown to the left.
Set the STV as follows:
• Input type 27, 28, or 29: 1 V
• Input type 30: −6 mV
Allow the count value on the No. 2 display to fully stabilize, then press the D Key to
temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and the count
value will not be temporarily registered.
7. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and wait two seconds
or press the M Key. This stores the temporarily registered calibration data to non-volatile
memory.
To cancel the saving of temporarily registered calibration data to non-volatile memory, press
the M Key (while no is displayed in the No. 2 display) without pressing the U Key.
8. The calibration mode is ended by turning the power OFF.
For Digital Controllers that have a transfer output, you can continue by calibrating the transfer
output. For detailed setting methods, refer to 7-6 Calibrating the Transfer Output.
E5@C Digital Temperature Controllers User's Manual (H174)