Shifting Input Values - Omron E5GC User Manual

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

5-1

Shifting Input Values

Shifting Inputs
You can set the Process Value Slope Coefficient and Process Value Input Shift parameters to
compensate the PV.
Process Value Input Shift
Process Value Slope Coefficient
• Calculating the Process Value Slope Coefficient and Process Value Input Shift
In the following equation, PVi is the input to the calculation, PVo is the result, INRT is the process
value slope coefficient, and INS is the process value input shift: PVo = (PVi × INRT) + INS
Moving Average
• The moving average operation reduces sudden changes in the input due to noise and other
factors, and can be enabled separately for each input.
• The Moving Average Count parameter is used for the moving average. It can be set to OFF, 2, 4,
8, 16, or 32.
• The default is OFF (disabled).
Input data
Parameter
Moving Average Count
*
The default is 8 for models other than the E5@C-@-0@.
E5@C Digital Temperature Controllers User's Manual (H174)
Parameter
Temperature input: −199.9 to 999.9
Analog input: −1,999 to 9,999
0.001 to 9.999
000
Time
Setting range
OFF, 2, 4, 8, 16, or 32
Setting range
Operation result
Unit
Times
5 Advanced Operations
Unit
Default
°C or °F
0.0
EU
0
None
1.000
Default
OFF*
5
5 - 3