3 Part Names and Basic Procedures
5
Set the set point.
* Hold the U (Up) or D (Down) Key to increment or decrement the value quickly.
6
Set the alarm set value or values.
Change the parameter that is displayed with the M (Mode) Key.
Alarm Type 2, 3, 6, 7, 8, 9,10, or 11
(Upper-limit Alarms and Lower-limit
Alarms)
Operation Level
This concludes the procedure to set the input type, alarm type, control method, set point, and alarm
set values. For information on the settings of the ON/OFF hysteresis, PID constants, HS alarm, HS
alarm, and other parameters, refer to Section 4 Basic Operation or Section 5 Advanced Operations.
3 - 20
al-1
Press the M (Mode)
0
Key several times to
display al-1 (AL-1).
Operation Display
25
0
25
Set point: 500°C (example)
500
Press the U (Up) and D
(Down) Keys and the S (Shift)
Key to change the value.
Alarm Type 1, 4, or 5 (Upper-limit and
Lower-limit Alarms or Upper-limit and
Lower-limit Range Alarms)
al1h
To set the alarm value
0
upper limit, press the M
(Mode) Key several times
to display al1h (AL1H).
al1l
To set the alarm value
lower limit, press the M
0
(Mode) Key several times
to display al1l (AL1L).
E5@C Digital Temperature Controllers User's Manual (H174)