Basic functions
3.16.2
QTY_BAD function block
3.16.2.1
Function block
Figure 56: Function block
3.16.2.2
Functionality
The QTY_BAD function block evaluates the quality bits of the input signal and
passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
3.16.2.3
Signals
Table 81: QTY_BAD Input signals
Name
IN
Table 82: QTY_BAD Output signals
Name
OUT
3.16.3

QTY_GOOSE_COMM function block

3.16.3.1
Function block
Figure 57: Function block
126
Type
Default
Any
0
Type
BOOLEAN
1MRS758755 C
Description
Input signal
Description
Output signal
REC615 & RER615
Technical Manual