Installing An Energy Pack - HPE ProLiant DL385 User Manual

Table of Contents

Advertisement

Product
HPE ProLiant server system ROM
HPE Smart Array SR controllers
HPE Smart Array MR controllers

Installing an energy pack

Prerequisites
Before you perform this procedure, make sure that you have the following items available:
T-10 Torx screwdriver
The components included with the hardware option kit
Storage controller backup power cable (ships with the storage controller)
Make sure that a Smart Array P-class Gen10 controller is installed.
If you are installing the HPE Smart Storage Hybrid Capacitor, verify that the system BIOS meets the minimum
firmware requirements.
Procedure
1.
Power down the server.
2.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3.
Do one of the following:
Extend the server from the rack.
Remove the server from the rack.
4.
Remove the access panel.
5.
Do one of the following:
Remove the air baffle.
If installed, remove the 4LFF midplane drive cage.
6.
Remove the fan cage.
7.
Install the energy pack.
Minimum firmware version
1.40
1.90
24.23.0-0041
Hardware options installation
106