Output Terminal Functions - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Output Terminal Functions

The digital multifunction outputs can be set for several functions using the H2-01 and H2-02 parameters (ter-
minal M1 to M4 function selection). These functions are described in the following section.
Related Parameters
Parameter
Number
H2-01
H2-02
During Run (Setting: 0) and During Run 2 (Setting: 37)
During Run (Setting: 0)
OFF
During Run 2 (Setting: 37)
OFF
These outputs can be used to indicate the Inverter's operating status.
Run command
Baseblock command
Output frequency
During run 1 output
During run 2 output
6-64
Name
Terminal M1-M2 function selection
Terminal M3-M4 function selection
The RUN command is OFF, the Inverter output is OFF
ON
The RUN command is ON, the Inverter output is giving out a voltage.
The Inverter does not give out a frequency. (During baseblock, DC injection or stopped)
ON
The Inverter gives out a frequency.
OFF
ON
OFF
OFF
ON
OFF
Fig 6.47 Timing Chart for During Run and During Run 2 Output
Setting
Range
0 to 3D
0 to 3D
ON
ON
Change
Factory
Access
during
Setting
Level
Operation
0
No
A
1
No
A