Smartgen HGM8140D User Manual page 27

Genset controller, display module, host module
Table of Contents

Advertisement

No.
Items
Disconnect
60
Frequency
Disconnect Engine
61
Oil Pressure
High Temp. Shut
62
Inhibit Enabled
Low OP Shut Inhibit
63
Enabled
64
AC System
Temperature
65
Sensor Curve
Pressure
66
Curve
Fuel Level Sensor
67
Curve
68
Poles
Temp.
69
Open Circuit Action
Oil
Pressure
70
Sensor
Circuit Action
Disconnect
71
Pressure Delay
72
Scheduled Run
73
Scheduled Period
74
Auto Start Inhibited
75
Auto Start Inhibited
76
Overload Action
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Parameters
Gen
(10-30)Hz
(0-400)kPa
(0-1)
(0-1)
(0-3)
(0-12)
Sensor
(0-12)
(0-7)
(2-64)
Sensor
(0-2)
Open
(0-2)
Oil
(0-20.0)s
(0-1)
(0-1)
(0-1)
(0-2)
(0-2)
Defaults
When generator frequency higher than the
14
set value, starter will be disconnected.
When generator oil pressure higher than the
200
set value, starter will be disconnected.
Factory default: when high temperature
0
occurs, shutdown alarm is initiated. Note 2
Factory default: when low oil pressure
0
occurs, shutdown alarm is initiated. Note 3
0: 3P4W; 1: 2P3W
0
2: 1P2W; 3: 3P3W
8
SGX, details to see Table 13.
8
SGX , details to see Table 13.
3
SGD, details to see Table 13.
Number of generator poles, which can be
4
used to speed calculating for gens without
speed sensors.
1
0:Not used ; 1:Warn; 2:Shutdown
When disconnect conditions include oil
pressure and engine oil pressure is higher
1
than disconnect oil pressure delay, the
genset is regarded as start successfully and
starter will disconnect.
When crank disconnect condition conclude
oil pressure, if engine oil pressure and delay
0.0s
value exceed pre-set crank disconnect
values, genset start successfully and starter
will disconnect.
0
0: Disabled; 1:Enabled
Monthly, weekly and daylily can be optional,
0
Start time and duration time can be
adjusted.
0
0: Disabled; 1:Enabled
Monthly, weekly and daylily can be optional,
0
Prohibit start time and duration time can be
adjusted.
0 Not used; 1 Warn; 2 Shutdown;
When the power exceeds preset limit, and
1
the duration is greater than the delay value,
over power alarm is active. Both return
value and delay value can be set.
Version 1.2
2019-09-12
Description
Page 27 of 56