No.
Items
Warning
Gen
Over
92
Warning
Gen Under Freq.
93
Warning
NOTE1: if "high temperature inhibit" is configured, or set auxiliary input as "inhibit high temperature stop" and this
input is active, when temperature is higher than the preset value, or high temperature alarm input is active, controller
will send warning signal only and not stop the unit.
NOTE2: if "low oil pressure inhibit" is configured, or set auxiliary input as "inhibit low oil pressure stop" and this input
is active, when oil pressure is lower than the preset value, or low oil pressure alarm input is active, controller will send
warning signal only and not stop the unit.
NOTE3: If default password (0318) isn‟t changed, it doesn‟t need to input when configuring parameters via PC
software; if the password is changed for the first time via PC software, it need to input password in password window.
NOTE4: Between input correct password and LCD back light haven‟t got dark, input parameter numbers can enter
parameter setting interface when enters "Password Input" again.
NOTE5: In teeth configuration interface, configure teeth status and power large than 20Hz, press start key for auto
calculating teeth numbers and press confirm key for changing teeth numbers.
No.
Item
00
Not Used
01
Common Alarm
02
Energise to Stop
03
Idle Control
04
Preheat Control
05
Close Gen Output
06
Reserved
07
Open
08
Speed Raise Relay
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Parameters
Freq.
(0-75.0)Hz
(0-75.0)Hz
Table 11 Relay Output Port 1-4 Contents
Output port is deactivated when "Not Used" is selected.
Include all shutdown alarms and warning alarms. When there is
warning alarm only, it is not self-lock; when a shutdown alarm
occurs, it is self-lock until the alarm is reset.
Suitable for genset with electromagnet and will active after "stop
idle delay". It is deactivated when the "ETS Solenoid delay"
expires.
Used for engine which has idles. Close before starting and open in
warming up delay; Close during stop idle delay and open when
stop is completed.
Close before starting and open before power up.
When close time is 0, it‟s continuous output.
When close time is 0, it‟s disabled.
Close when the generator enters into Warming Up delay (close
time: warming up delay).
Defaults
lasts for 5s, under voltage is considered and
under volt warning is initiated. When it is set
to 30V, under voltage signal is not detected.
When gen freq is higher than this and last
55.0
for 5s, over freq is considered and over freq
warning is initiated.
When gen freq is lower than this, but not 0
42.0
and lasts for 5s, under freq is considered
and under freq alarm is initiated.
Description
Version 1.2
2019-09-12
Description
Page 29 of 56