Smartgen HGM8140D User Manual page 14

Genset controller, display module, host module
Table of Contents

Advertisement

No.
Type
12
High Temperature
13
Low Oil Pressure
14
Digital Input
15
Fail to Charge
16
Over Power
17
ECU Warn
RS232
18
Communication Fail
CAN Exp.
19
Communication Fail
Programmable
20
Sensor 1 Open
Programmable
21
Sensor 1 High
Programmable
22
Sensor 1 Low
23
Reverse Power
High Temp.
24
Warning Input
25
Low Oil Pressure
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
When it is enabled and the controller detects that config. sensor
temperature (sensor type: temperature sensor) has exceeded the
pre-set value, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
When it is enabled and the controller detects that config. sensor oil
pressure (sensor type: oil pressure sensor) has fallen below the pre-set
value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the switching input is selected as user-defined and action is
warning, when input port is active, the controller will initiate
corresponding warning alarms.
When controller detects the fail to charge warn input is active, it will
send alarm signals and the corresponding alarm information will be
displayed on LCD.
When controller detects the genset power value (power is positive) is
higher than the set value and the action select warn, it will send warn
signals.
When controller gets the warn signals from engine via J1939, it will
send warn signals.
When multi display modules are connected and RS232 port
communication fail warning is active, controller will initiate warning
alarms if RS232 port display fail to communication, and the
corresponding information will displayed on the LCDs of other CAN port
display modules.
When multi display modules are connected and CAN Expansion
displays communication fail warning is active, controller will initiate
warning alarms if CAN display module fail to communication, and the
corresponding information will displayed on the LCDs of other display
modules.
When the controller detects that the sensor is open circuit and the
action select "Warn", it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When it is enabled, and controller detects the sensor value is higher
than the setting threshold value, controller will initiate warning signals.
When it is enabled, and controller detects the sensor value is lower
than the setting threshold value, controller will initiate warning signals.
When reverse power detection is active, and controller detects the
reverse power value of genset(power is negative) is over than setting
threshold, and selection is warn, controller will initiate warning signals.
When it is enabled and high temperature shutdown is prohibited or high
temperature of input port shutdown is prohibited, controller will initiate a
warning alarm and the corresponding alarm information will be
displayed on LCD.
When it is enabled and low oil pressure shutdown is prohibited or low
Version 1.2
Description
2019-09-12
Page 14 of 56