Smartgen HGM8140D User Manual page 7

Genset controller, display module, host module
Table of Contents

Advertisement

Accumulate total generator power kWh
For generator, controller has over and under voltage, over and under frequency, over current
and over power detection functions.
Precision measure and display parameters about Engine.
Temp. (WT)
Oil Pressure (OP)
Fuel Level (FL)
Speed (RPM)
Voltage of Battery
Voltage of Charger
Hour count accumulation
Start times accumulation
Protection: automatic start/stop of the gen-set, ATS (Auto Transfer Switch) control with
perfect fault indication and protection function.
With ETS (energize to stop), idle control, pre-heat control and rise/drop speed control
functions, which are all relay outputs.
Parameter setting: parameters can be modified and stored in internal FLASH memory and
cannot be lost even in case of power outage; most of them can be adjusted using front panel
of the controller and also can be modified using PC via USB or RS485 port.
Multiple temperature, pressure, oil pressure sensor can be used and self-defined directly.
Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are
optional.
All display interfaces can be adjusted.
With emergency start function, which can be achieved by input port (Emergency Start) or
press manual button and start button simultaneously on the panel. This function is used in the
status of very low temperature in the winter and start genset manually in a very long time.
With battle mode, all shutdown alarms except for emergency shutdown and over speed
warning alarms are inhibited
With flywheel tooth number automatic recognition function.
Widely power supply range DC(8~35)V, suitable to different starting battery voltage
environment.
All parameters used digital adjustment, instead of conventional analog modulation with
normal potentiometer, more reliability and stability.
With maintenance function. Types (date and running time) can be optional and actions
(warning, shutdown or trip and stop) can be set when maintenance time out.
Event log function. Maximum 99 event logs can be memorized.
Data analysis function. 5 circular logs and genset detailed data in one minute before
shutdown alarms.
Real-time clock, scheduled start & stop generator (can be set as start genset once a
day/week/month whether with load or not)
Waterproof security level IP65 due to rubber seal installed between the controller enclosure
and panel fascia;
Modular design, anti-flaming ABS plastic enclosure, pluggable connection terminals and
embedded installation way; compact structure with easy mounting.
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
° C/° F both be displayed
kPa/psi/bar all be displayed
%(unit)
Fuel Quantity Left L(unit)
r/min (RPM)
V (unit)
V (unit)
Version 1.2
2019-09-12
Page 7 of 56