Smartgen HGM8140D User Manual page 36

Genset controller, display module, host module
Table of Contents

Advertisement

No.
Type
16
Remote Control Mode
Charge
Alt
17
Warning
18
Reserved
19
Alarm Mute
20
Idle Control Mode
21
60Hz Select
22
Rise Speed Pulse
23
Drop Speed Pulse
24
Forced Manual Start
25
Inhibit Alarm Stop
26
Reserved
27
Instrument Mode
RS232 Display Control
28
Enable
CAN-1 Display Control
29
Enable
CAN-2 Display Control
30
Enable
CAN-3 Display Control
31
Enable
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
will automatically start or stop according to the remote start input.
When input is active, all keys except for
panel of HGM8140 are inactive and remote control mode will
display on the LCD.
Failure
Connected to charge alt failure output port.
When input is active, "Audible Alarm" output can be inhibited.
Idle control output when input is active.
Used for genset with CANBUS interface. When it is active,
frequency is 60Hz.
It is used for GTSC1 electronic fuel injection engine, when it is
active, engine speed will increase 50rpm.
It is used for GTSC1 electronic fuel injection engine, when it is
active, engine speed will decrease 50rpm.
When it is active, genset will be forced started, details please to see
Emergency Start.
All shutdown alarms are prohibited except for the emergency
shutdown.
All outputs are prohibited in this mode.
When it is active, hose control function can be realized by the
displayed HGM8140D module on RS232 port.
When it is active, hose control function can be realized by the
displayed HGM8140D module on CAN-1 port.
When it is active, hose control function can be realized by the
displayed HGM8140D module on CAN-2 port.
When it is active, hose control function can be realized by the
displayed HGM8140D module on CAN-3 port.
Version 1.2
Description
2019-09-12
on the
Page 36 of 56

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm8140Hgm8140m

Table of Contents