Beckhoff EPP3504-0023 Short Manual page 68

4-channel measuring bridge,(sg) full/half/quarter bridge, 24 bit, 10 ksps
Hide thumbs Also See for EPP3504-0023:
Table of Contents

Advertisement

Commissioning
Index
Name
(hex)
80n0:04
Start
Connection Test
80n0:08
Enable Shunt
Calibration
80n0:13
Wire Resistance
Compensation
80n0:16
Filter 1
80n0:17
Average Filter 1
No of Samples
80n0:18
Decimation
Factor
80n0:19
Filter 2
80n0:1A
Average Filter 2
No of Samples
80n0:1B
True RMS No.
of Samples
80n0:1C
Enable True
RMS
68
Meaning
9 - 4.5 V
10 - 5.0 V
65535 - External Supply
Start connection test with rising
edge (see section "Broken wire
detection/ optional connection
diagnosis")
Shunt calibration (Enable/ Disable) BOOLEAN
Wire Resistance Compensation
Options for filter 1:
0 – None
1 - FIR Notch 50 Hz
2 - FIR Notch 60 Hz
3 - FIR LP 100 Hz
4 - FIR LP 1000 Hz
5 - FIR HP 150 Hz
16 - IIR Notch 50 Hz
17 - IIR Notch 60 Hz
18 - IIR Butterw. LP 5th Ord. 1 Hz
19 - IIR Butterw. LP 5th Ord. 25 Hz
20 - IIR Butterw. LP 5th Ord. 100
Hz
21 - IIR Butterw. LP 5th Ord. 250
Hz
22 - IIR Butterw. LP 5th Ord. 1000
Hz
32 - User defined FIR Filter
33 - User defined IIR Filter
34 - User defined Average Filter
Number of samples for user-
defined Average Filter 1
Factor of the individual sampling
rate (min. 1)
Options for filter 2:
0 - None
1 - IIR 1
2 - IIR 2
3 - IIR 3
4 - IIR 4
5 - IIR 5
6 - IIR 6
7 - IIR 7
8 - IIR 8
16 - User defined FIR Filter
17 - User defined IIR Filter
18 - User defined Average Filter
Number of samples for user-
defined Average Filter 2
Number of samples for "True RMS"
calculation (min. 1, max. 1000);
also see chapter TrueRMS
Activation of "True RMS"
calculation
Version: 1.2
Data type
Flags
Default
BOOLEAN
RW
0x00 (FALSE)
RW
0x00 (FALSE)
REAL32
RW
0x00000000 (0.0)
UINT16
RW
0x0000 (0
UINT16
RW
0x0001 (1
UINT16
RW
0x0001 (1
UINT16
RW
0x0000 (0
UINT16
RW
0x0001 (1
UINT16
RW
0x0001 (1
BOOLEAN
RW
0x00 (FALSE)
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
EPP3504-0023