Beckhoff EPP3504-0023 Short Manual page 224

4-channel measuring bridge,(sg) full/half/quarter bridge, 24 bit, 10 ksps
Hide thumbs Also See for EPP3504-0023:
Table of Contents

Advertisement

Appendix
Text ID
Type
Place
0x441A
Warning
Drive
0x441B
Warning
Drive
0x441C
Warning
Drive
0x4600
Warning
General IO
0x4610
Warning
General IO
0x4705
Warning
0x470A
Warning
Text ID
Type
Place
0x8000
Error
System
0x8001
Error
System
0x8002
Error
System
0x8003
Error
System
0x8004
Error
System
0x8005
Error
System
0x8006
Error
System
0x8007
Error
System
0x8100
Error
General
0x8101
Error
General
0x8102
Error
General
0x8103
Error
General
0x8104
Error
General
0x8105
Error
General
0x8135
Error
General
0x8136
Error
General
0x8137
Error
General
0x8140
Error
General
0x8141
Error
General
0x8142
Error
General
0x8143
Error
General
0x817F
Error
General
0x8200
Error
Communication Write access error: %d, %d
0x8201
Error
Communication No communication to field-side
0x8281
Error
Communication Ownership failed: %X
0x8282
Error
Communication To many Keys founded
0x8283
Error
Communication Key Creation failed: %X
224
Text Message
Limit: Motor I2T-model exceeds
100%%
Limit: Velocity limitation
STO while the axis was enabled
Wrong supply voltage range
Wrong output voltage range
Processor usage at %d %%
EtherCAT Frame missed (change
Settings or DC Operation Mode
or Sync0 Shift Time)
Text Message
%s: %s
Error: 0x%X, 0x%X, 0x%X
Communication aborted
Configuration error: 0x%X, 0x%X,
0x%X
%s: Unsuccessful FwdOpen-
Response received from %d.%d.
%d.%d (%s) (Error: %u)
%s: FwdClose-Request sent to
%d.%d.%d.%d (%s)
%s: Unsuccessful FwdClose-
Response received from %d.%d.
%d.%d (%s) (Error: %u)
%s: Connection with %d.%d.%d.
%d (%s) closed
Status word set: 0x%X, %d
Operation mode incompatible to
PDO interface: 0x%X, %d
Invalid combination of Inputs and
Outputs PDOs
No variable linkage
Terminal-Overtemperature
PD-Watchdog
Cycle time has to be a multiple of
125 µs
Configuration error: invalid
sampling rate
Electronic type plate: CRC error
Sync Error
Sync%X Interrupt lost
Sync Interrupt asynchronous
Jitter too big
Error: 0x%X, 0x%X, 0x%X
(Auxiliary voltage missing)
Version: 1.2
Additional comment
Limit: Motor I2T-model exceeds 100%
The threshold values for the maximum speed were
exceeded.
An attempt was made to activate the axis, despite the
fact that no voltage is present at the STO input.
Supply voltage not in the correct range
Output voltage not in the correct range
Processor load at %d %%
EtherCAT frame missed (change DC Operation Mode
or Sync0 Shift Time under Settings)
Additional comment
General error; parameters depend on event. See
device documentation for interpretation.
Communication aborted
General; parameters depend on event.
See device documentation for interpretation.
Error bit set in the status word
Mode of operation incompatible with the PDO interface
Invalid combination of input and output PDOs
No variables linked
The internal temperature of the terminal exceeds the
parameterized error threshold. Activation of the
terminal is prevented
Communication between the fieldbus and the output
stage is secured by a Watchdog. The axis is stopped
automatically if the fieldbus communication is
interrupted.
• The EtherCAT connection was interrupted during
operation.
• The Master was switched to Config mode during
operation.
The IO or NC cycle time divided by 125 µs does not
produce a whole number.
Configuration error: Invalid sampling rate
Content of the external name plate memory invalid.
Real-time violation
Sync%X Interrupt lost
Sync Interrupt asynchronous
Jitter limit violation
Error while writing
• There is no voltage applied to the power contacts.
• A firmware update has failed.
EPP3504-0023